首页> 外文会议>Conference on Precision Electromagnetic Measurements >Testing Electric Utility Smart Meters with High Harmonic Current Waveforms
【24h】

Testing Electric Utility Smart Meters with High Harmonic Current Waveforms

机译:用高谐波电流波形测试电力智能仪表

获取原文

摘要

This paper describes the results from testing the accuracy of electric utility smart meters. The results compare the smart meter measurements of voltage and current waveforms of a fundamental 60 Hz frequency with energy usage that contains current signals with narrow spikes. The Fourier component analysis of the current spikes requires high harmonic frequency analysis. A separate, precision power analyzer was calibrated as the reference. The worst-case error of about 3% was measured for three similar model meters out of twelve meters, where the uncertainty was about 0.1%.
机译:本文介绍了对电力智能仪表的准确性进行测试的结果。结果将智能电表对60 Hz基本频率的电压和电流波形的测量结果与包含尖峰电流信号的能量使用情况进行了比较。电流尖峰的傅立叶分量分析需要高谐波频率分析。校准了一个单独的精密功率分析仪作为参考。对于十二米中的三个相似的模型米,测得的最坏情况误差约为3%,不确定度约为0.1%。

著录项