Evaluation of Distribution Class Transformers Using Narrow Band Dielectric Frequency Response Measurements

机译:使用窄带介电频率响应测量评估配电类变压器

获取原文

摘要

The analysis and diagnostics of power and distribution transformers has been performed primarily by time and frequency domain methods. In the frequency domain, power factor or dissipation factor at line frequency is a method widely used but one single measurement at line frequency encounters limitations to analytical and qualitative interpretation of the insulation of a variety of electrical equipment. With the benefits found by wide band dielectric frequency response, the need to incorporate a method capable of better condition assessment in very short time is required in the field. Narrow Band Dielectric Frequency Response (NB DFR) is a series of dielectric loss measurements performed in a narrow frequency band typically between 1 and 500 Hz or even up to 1 kHz, at a low voltage. In 2015, Southern California Edison began utilizing NB DFR for dielectric loss measurements in the interwinding insulation in condition assessment of used distribution class transformers. The scope of the work included thermal accelerated aging subjecting the transformers different levels of overload while using NB DFR to document changes in the dielectric response as the oil and paper throughout the process. Based on the experimental results obtained, authors provide throughout this document an analytical procedure to evaluate the NB DFR described as a plot of PF/DF as a function of frequency as well as capacitance (C) as a function of frequency. Most important is to consider the factors influencing the changes in the dielectric response after scheduled thermal accelerated aging. On the basis of specific characteristics observed within the plot, definite assertions may be made in regards to the condition of the cellulose and oil. This work reflects the benefits of NB DFR to evaluate the aging process of oil-paper insulation in comparison to conventional line frequency power factor testing.
机译:电力和配电变压器的分析和诊断主要是通过时域和频域方法进行的。在频域中,线路频率上的功率因数或损耗因数是一种广泛使用的方法,但是线路频率上的单个测量会遇到各种电气设备绝缘的分析和定性解释方面的局限性。借助宽带介电频率响应所带来的好处,在现场需要结合一种能够在非常短的时间内进行更好状态评估的方法。窄带介电频率响应(NB DFR)是在低电压下通常在1至500 Hz或什至高达1 kHz的窄频带中执行的一系列介电损耗测量。 2015年,南加州爱迪生公司开始将NB DFR用于绕组间绝缘中的介电损耗测量,以评估二手配电级变压器的状态。工作范围包括热加速老化,使变压器承受不同程度的过载,同时使用NB DFR记录油和纸在整个过程中介电响应的变化。基于获得的实验结果,作者在整个文档中提供了一种分析程序,以评估NB DFR,将其描述为PF / DF与频率的关系图以及电容(C)与频率的关系图。最重要的是要考虑计划的热加速老化后影响介电响应变化的因素。根据曲线图中观察到的特定特征,可以对纤维素和油的状况做出明确的断言。这项工作反映了NB DFR与传统的线路频率功率因数测试相比,可以评估油纸绝缘的老化过程。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号