Future active distribution grids will be characterized by rapid and significant changes of operation and behavior due to, for example, intermittent power injections from renewable sources and the load-generation characteristic of the so-called prosumers. The design of a robust measurement infrastructure is critical for safe and effective control and operation. In previous works, the authors proposed a placement procedure that allows finding an optimal measurement location incorporating Phasor Measurement Units (PMUs) and smart metering devices for distribution system state estimation (DSSE). In this paper the concept of robustness is introduced in the optimal meter placement procedure, so that the distributed measurement system can provide accurate estimates also in the occurrence of either loss of data or degradation of metrological performance of the measurement devices. Tests performed on a small UKGDS 16-bus distribution network are presented and discussed.
机译:由于可再生来源的间歇性功率注射以及所谓的监管的负载发电特征,将来的运行和行为的快速和显着变化的特征在于,运行和行为的快速变化。稳健的测量基础设施的设计对于安全有效的控制和操作至关重要。在以前的作品中,作者提出了一个放置程序,允许找到包含分析系统(PMU)和用于分配系统状态估计(DSSE)的Phasor测量单元(PMU)和智能计量装置的最佳测量位置。在本文中,在最佳仪表放置过程中引入了鲁棒性的概念,使得分布式测量系统也可以在发生数据丢失或测量装置的计量性能的劣化时提供准确的估计。提出并讨论了对小型UKGDS 16总线分配网络执行的测试。