The parallel hybrid converter (PHC) is gaining popularity for high voltage direct current applications. The chain-links (CLs) in the PHC bear only a fraction of the output phase current and exhibit double frequency nature. This reduces the energy storage requirement and the losses occurring in the CLs of the PHC. The PHC converter also requires lower number of sub-modules (SMs) and switching devices. The existing PHC configuration requires harmonic voltage injection in the CLs to feed the ac grid, thereby injecting harmonic currents into the main DC-link and it is not dc fault-tolerant. A new front-front dc-dc hybrid configuration for high voltage transmission systems using PHC is presented, which eliminates the need for harmonic voltage injection. The proposed dc-dc configuration is dc fault-tolerant and requires reduced SM capacitors size and smaller interlinking transformers owing to high-frequency switching operation. The authenticity of the proposed dc-dc converter is verified by caring out various simulation and hardware studies.
机译:并行混合转换器(PHC)在高压直流应用中越来越受欢迎。 PHC中的链节(CL)仅承受输出相电流的一小部分,并具有双频特性。这减少了能量存储需求以及在PHC的CL中发生的损耗。 PHC转换器还需要较少数量的子模块(SM)和交换设备。现有的PHC配置要求在CL中注入谐波电压以向交流电网供电,从而将谐波电流注入到主直流母线中,并且它不是直流容错的。提出了一种新的用于使用PHC的高压输电系统的前-前DC-DC混合配置,从而消除了对谐波电压注入的需求。提议的dc-dc配置具有dc容错能力,并且由于高频开关操作,因此需要减小SM电容器的尺寸并减小互连变压器的尺寸。通过进行各种仿真和硬件研究,可以验证所提出的DC-DC转换器的真实性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号