Fault Analysis of The Distance Protection Overreach Caused by The Power Transmission Lines Ring Closing with A Wrong Phase Sequence

机译:用错误相位序列关闭电力传输线响起距离保护辐射的故障分析

获取原文

摘要

A power transmission lines ring closing with a wrong phase sequence occurred in a regional power grid, which led to an overreach of the line distance protection. Through theoretical analysis, it is found that when the lines ring closing is operated with a wrong phase sequence, the protection shows the similar electrical characteristics as the phase-to-phase short circuit, and there is an equivalent phase-to-phase fault point in the system, which is the midpoint of all equivalent impedances between the power supply on both sides. As a result, the equivalent measured impedance may fall into the action range of the distance protection somewhere, which will lead to the exceeding of distance protection. The actual fault data also confirm the analysis conclusion.
机译:具有错误相位序列的电力传输线闭合在区域电网中发生,这导致了线距离保护的溢出。 通过理论分析,发现线圈闭合用错误的相位序列运行时,保护显示与相位到相位短路相似的电特性,并且存在等效的相位到相位故障点 在系统中,这是两侧电源之间的所有等效阻抗的中点。 结果,等效测量阻抗可能落入某个地方的距离保护的动作范围,这将导致超出距离保护。 实际故障数据也证实了分析结论。