首页> 外文会议>IEEE PES Asia-Pacific Power and Energy Engineering Conference >Study on current sharing characteristics of arrester for UHV DC
【24h】

Study on current sharing characteristics of arrester for UHV DC

机译:特高压直流避雷器的均流特性研究

获取原文

摘要

The arresters are generally connected in parallel by the same type of multi-column arrester. Therefore, when the arrester absorbs energy, the distribution of energy between the arresters of each column is one of the key problems for the stable operation of the multi-column parallel arrester. According to the provisions of GB/T 22389-2010, this paper analyzes the factors affecting the uneven current distribution. The difference of U1mA should be as small as possible. The ATP and MATLAB software are used to simulate the current sharing characteristics of the 38-column parallel arrester. The volt-ampere characteristic curve band of the arrester, the non-uniformity coefficient of the arrester current of each column in this area is less than 1.1; meanwhile, the volt-ampere characteristic of the arrester in this area is calculated, and the voltage difference percentage at 20 mA is 0.456%.
机译:避雷器通常由相同类型的多柱避雷器并联连接。因此,当避雷器吸收能量时,每列避雷器之间的能量分配是多柱并联避雷器稳定运行的关键问题之一。根据GB / T 22389-2010的规定,分析影响电流分布不均的因素。 U1mA的差异应尽可能小。 ATP和MATLAB软件用于模拟38柱并联避雷器的均流特性。避雷器的伏安特性曲线带,该区域每一列的避雷器电流的不均匀系数均小于1.1;同时,计算了该区域避雷器的伏安特性,20 mA时的电压差百分比为0.456%。