首页> 外文会议>International Conference on Modern Power Systems >A Numerical Analysis of the Harmonic Impedance in a Medium Voltage AC Network
【24h】

A Numerical Analysis of the Harmonic Impedance in a Medium Voltage AC Network

机译:中压交流网络中谐波阻抗的数值分析

获取原文

摘要

Under the current conditions of the increasing harmonic pollution of three-phase distribution networks, the correct determination of the harmonic impedance of a network in a section or in a consumer bus becomes more and more important. This is due to the importance of harmonic impedance used as a tool of analysis and basing of the solutions required to increase the network performance, including the power quality delivered to consumers. The article uses the results of the numerical analysis applied in a case study performed for a medium voltage distribution network, like a real one, in order to demonstrate that the underground electrical lines of relatively long lengths significantly influence the harmonic modelling of the network and the correctness of the harmonic impedance values. In addition, the model of such a line must consider the distributed equivalent parameters, which becomes an imperative requirement when seeking to obtain the correct values for the equivalent harmonic impedance of the network.
机译:在当前条件下,三相配送网络的谐波污染的增加,正确确定网络中网络的谐波阻抗或消费者总线变得越来越重要。这是由于谐波阻抗作为分析工具的重要性,并且基于增加网络性能所需的解决方案,包括向消费者提供的电能质量。本文使用在为中压配电网执行的案例研究中应用的数值分析结果,如真实的,以便证明相对长的长度的地下电线显着影响网络的谐波建模和谐波阻抗值的正确性。另外,这种线的模型必须考虑分布式等效参数,该参数成为当寻求获得网络等同谐波阻抗的正确值时成为必要的要求。