首页> 外文会议>International Conference on Intelligent Transportation, Big Data and Smart City >Numerical Study the Performance of Jet Fans in Utility Tunnel Ventilation
【24h】

Numerical Study the Performance of Jet Fans in Utility Tunnel Ventilation

机译:电站通风中射流风机性能的数值研究

获取原文

摘要

The urban utility tunnel needs efficient ventilation systems, which contributes to maintain air quality in the utility tunnel. In order to improve ventilation performance, the jet fans were used in the utility tunnel. Fluent 14.0 and k-ε turbulence model were applied to research the ventilation performance with jet fan with a deflected angle. Results showed that the air velocity is higher in the upstream of fire source than in downstream fire source. Typically, the deflected angle of jet fan has a certain effect on the velocity and temperature distribution of air in utility tunnel. The optimal deflected angle of jet fans was γ=12° near the fire source.
机译:城市公用事业隧道需要有效的通风系统,这有助于维持公用事业隧道中的空气质量。为了改善通风性能,在公用隧道中使用了喷射风扇。采用Fluent 14.0和k-ε湍流模型研究了偏角射流风机的通风性能。结果表明,火源上游的空气流速高于下游火源。通常,射流风扇的偏转角会对公用事业隧道中空气的速度和温度分布产生一定的影响。在火源附近,喷气风扇的最佳偏转角为γ= 12°。