首页> 外文会议>IEEE Power and Energy Society General Meeting >The Influence of Location of Distributed Energy Storage Systems on Primary Frequency Response of Low Inertia Power Systems
【24h】

The Influence of Location of Distributed Energy Storage Systems on Primary Frequency Response of Low Inertia Power Systems

机译:分布式储能系统位置对低惯性电力系统一次频率响应的影响

获取原文

摘要

The paper investigates the impact of primary frequency response (PFR) support, provided by distributed energy storage systems (ESS), depending on their location in low inertia power systems. The analysis is performed for three operating conditions of the network. For each operating condition, the decrease in the network load is balanced by disconnecting a part of synchronous generation (SG) that reduces the system inertia and increases the proportion of RES. The uncertainties in power generation of renewable energy sources (RES) and loading forecast are also incorporated into simulations.The results clearly show that the effect of location of ESS on PFR is negligible if the inertia of the system is not substantially reduced. However, when the proportion of RES becomes greater than SG, the ESS installed in the lowest inertia provide significantly better PFR support to the system. The studies are performed in a modified 16 machine and 68 bus network.
机译:本文研究了分布式能量存储系统(ESS)提供的主频率响应(PFR)支持的影响,具体取决于它们在低惯性电力系统中的位置。针对网络的三个操作条件执行分析。对于每种运行状况,通过断开同步发电(SG)的一部分来平衡网络负载的减少,这会减小系统惯性并增加RES的比例。模拟中还包含了可再生能源发电(RES)的不确定性和负荷预测。结果清楚地表明,如果系统的惯性没有显着降低,则ESS的位置对PFR的影响可以忽略不计。但是,当RES的比例大于SG时,以最低惯性安装的ESS为系统提供了更好的PFR支持。研究在改良的16机和68总线网络中进行。