【24h】

PERFORMANCE EVALUATION OF PLATE HEAT EXCHANGER WITH H_2O/LiBr REFRIGERANT

机译:H_2O / LiBr制冷剂板式换热器性能评估

获取原文

摘要

In this study, the heat transfer characteristics of Water/Lithiumbromide(LiBr) solution in the plate heat exchanger (PHE) for the absorption chiller application is evaluated. The plate heat exchanger is arranged in single-pass, counter flow and chevron angle of the corrugated plate is 78.5°. The H_2O/LiBr solution as the working fluid was used with concentration ranging from 52.40% to 64.92%, Reynolds number ranging between 27.29 and 255.1 and Prandtl number ranging between 4.59 and 19.26. The experiment was conducted within ±10% energy balance error range. As a result, the heat transfer coefficient was evaluated ranging from 0.68 kW/m~2-K to 2.92 kW/m~2-K. Based on the experimental data, the empirical heat transfer correlation of the H_2O/LiBr solution is developed and applicable within ±20% error range. By comparing with the correlations of the others, the validity of the heat transfer correlation of this study is validated.
机译:在这项研究中,评估了水/溴化锂(LiBr)溶液在板式换热器(PHE)中用于吸收式制冷机的传热特性。板式换热器以单程布置,逆流且波纹板的人字形角为78.5°。使用H_2O / LiBr溶液作为工作流体,其浓度范围为52.40%至64.92%,雷诺数范围为27.29至255.1,普朗特数范围为4.59至19.26。实验在±10%的能量平衡误差范围内进行。结果,传热系数的评估范围为0.68 kW / m〜2-K至2.92 kW / m〜2-K。根据实验数据,建立了H_2O / LiBr溶液的经验传热相关性,适用于±20%的误差范围。通过与其他相关性的比较,验证了本研究传热相关性的有效性。