Study on Interference of Partial Discharge Test of 750kV Shunt Reactor in Substation

机译:750kV分流反应器局部放电试验在变电站中的干扰研究

获取原文

摘要

In order to judge the state of main insulation and turn-to-turn insulation of 750kV shunt reactors in operation. An on-site partial discharge test method for 750kV shunt reactor based on frequency conversion power supply and series resonance technology was put forward in this paper and used in the field test in Xining 750kV substation. Partial discharge test is the most effective method to detect the insulation status of high voltage equipment. It could help to find the insulation defects timely and increase the reliability of electrical equipment in operation. There is no precedent for the on-site partial discharge test of 750kV shunt reactor before because related test equipment in traditional method is too bulky and heavy to place in substation. Due to the wide application of variable frequency series resonance technology, the on-site partial discharge test of 750kV shunt reactor can be carried out. The test results show that the partial discharge capacity of tested shunt reactor is lower than standard value, but main parts of the PRPD map are filled with interference signals. It is difficult to identify the partial discharge signal from tested reactor because of the bad electromagnetic environment and complex interference in the substation. Therefore, the possible interference factors in the test such as corona discharge of adjacent high voltage transmission lines, higher harmonic interference of power supply and loop coupled interference are analyzed in this paper.
机译:为了判断750kV滑顺式反应器的主绝缘和转弯绝缘的状态。本文提出了一种基于变频电源和串联谐振技术的750kV分流抗反应器的现场局部放电试验方法,并用于西宁750kV变电站的现场测试。局部放电测试是检测高压设备绝缘状态的最有效方法。它有助于及时找到绝缘缺陷,并提高操作中电气设备的可靠性。在现场局部放电试验中没有先例的750kV分流反应器之前,因为传统方法中的相关测试设备太大而沉重,以便在变电站中放置。由于可变频率序列谐振技术的广泛应用,可以进行750kV分流抗体的现场局部放电试验。测试结果表明,经过测试的分流抗体的部分放电容量低于标准值,但PRPD地图的主要部分填充有干扰信号。由于电磁环境不良和变电站的复杂干扰,难以识别来自测试反应器的局部放电信号。因此,本文分析了相邻高压传输线的电晕放电等测试中的可能的干扰因素,在本文中分析了电源和环路耦合干扰的更高谐波干扰。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号