In this work, Finite Element analysis is carried out on an outdoor High Voltage (HV) glass insulator string exposed to acid precipitation using Comsol Multiphysics. The pH of the acid was varied over a range of 2.5 and 5.5 and its effect on electric field distribution and heat generation studied. This pH range was chosen to represent recorded values of rainfall acidity in the field. High electric fields where observed at lower pH levels, exceeding the threshold value for partial discharge (PD). These high electric fields where observed at insulator discs closest to the HV terminal of the insulator string. Also, heat generation increased with increased rain acidity, where flow of leakage current is increased. These results can be applied to laboratory experiments and field tests designed to investigate the performance of HV insulators installed in heavy industrial areas and exposed to acid rain pollution.
机译:在这项工作中,使用Comsol Multiphysics对暴露于酸沉淀的室外高压(HV)玻璃绝缘子串进行了有限元分析。酸的pH值在2.5到5.5范围内变化,并且研究了其对电场分布和热量产生的影响。选择该pH范围以代表现场的降雨酸度记录值。在较低的pH值下观察到的高电场,超过了局部放电(PD)的阈值。在最靠近绝缘子串HV端子的绝缘子盘处观察到的这些高电场。同样,随着雨水酸度的增加,热量的产生也随之增加,其中泄漏电流的流量也增加了。这些结果可用于实验室研究和现场测试,旨在研究安装在重工业区并暴露于酸雨污染的高压绝缘子的性能。