摘要

Working under PWM pulse voltage, medium voltage medium/high-frequency transformers may face unevenly distributed electrical stress between inter-turns. This could increase the probability of partial discharge in the winding insulation and thus the risk of premature insulation failure would be higher. To investigate this issue, an equivalent circuit model of a transformer's winding is built. Based on that, simulations on voltage distribution between inter-turns with different voltage rise times, frequencies, material relative permittivity, insulation distance, and number of turns are conducted. The results show that uneven voltage distribution exists in the winding of transformers operating under PWM pulse voltage, with the first two turns suffering from the highest voltage drop. Also, the influence of the above-mentioned parameters on the inter-turn voltage distribution is revealed.
机译:在PWM脉冲电压下工作,中电压介质/高频变压器可能面临匝间之间的不均匀分布的电力应力。这可以提高绕组绝缘中局部放电的概率,因此过早绝缘失效的风险将更高。为了调查这个问题,建立了一个变压器绕组的等效电路模型。基于此,对具有不同电压上升时间的匝间之间的电压分布的模拟,进行频率,材料相对介电常数,绝缘距离和匝数。结果表明,在PWM脉冲电压下工作的变压器绕组中存在不均匀的电压分布,前两轮恢复最高电压下降。而且,揭示了上述参数对匝间电压分布的影响。