首页> 外文会议>IEEE International Conference on High Voltage Engineering and Application >Mechanical Condition Assessment of Vacuum On-load Tap-changer for Converter Transformer based on time-frequency domain characteristics of Vibration Signal
【24h】

Mechanical Condition Assessment of Vacuum On-load Tap-changer for Converter Transformer based on time-frequency domain characteristics of Vibration Signal

机译:基于时频域特性的振动信号时频域特性,对变压器变压器真空载载分接开关的机械条件评估

获取原文

摘要

In this paper, according to the structural characteristics of vacuum on-load tap-changer for converter transformer, vibration test was carried out during switching process in the field. Vibration characteristics in the time domain and frequency domain were studied. Based on the time-frequency domain characteristics of the vibration signal, a method to evaluate the condition of vacuum on-load tap-changer(OL TC) for converter transformer is proposed, and its engineering validity is verified. This method was proved to be effectively detect mechanical defects of vacuum OLTC, such as abnormal motor-drive mechanism, broken supporting-plate and crack of base of shock absorber.
机译:本文根据用于转换器变压器的真空上载分接开关的结构特性,在该领域的开关过程中进行振动测试。研究了时域和频域中的振动特性。基于振动信号的时频域特性,提出了一种评价用于转换器变压器的真空上载分接开关(OL TC)的方法,验证了其工程有效性。证明该方法有效地检测真空OLTC的机械缺陷,例如电动驱动机构的异常异常,支撑板和减震器基部的裂缝。