首页> 外文会议>IEEE International Conference on High Voltage Engineering and Application >Study on the reliability of 10kV uninterrupted maintenance outgoing switchgear under the condition of main device switching to the back-up device
【24h】

Study on the reliability of 10kV uninterrupted maintenance outgoing switchgear under the condition of main device switching to the back-up device

机译:在备份装置的主设备条件下10kV不间断维护开关可靠性研究

获取原文

摘要

Very large overcurrent and overvoltage will occur when the disconnectors switching the main device to backup device for live maintenance, which will threaten the reliability of the switchgear. Therefore, a research about the reliability of switchgear under the switching condition is carried out. Based on the analysis of the transient switching process, the overcurrent and overvoltage are obtained. Then, a 3D FEM model to study the insulating properties and temperature rise characteristics of the switchgear are set up respectively, and the electric field and temperature rise are calculated. The results show that: 1) 17.3kV overvoltage and 1.42kA overcurrent are generated during the switching process;2) The maximum field strength and temperature rise can reach 3.65 kV / cm and 65K respectively, which still meet the requirement of switchgear design standard.
机译:当隔离电路将主设备切换为实时维护的备用设备时,将发生非常大的过电流和过电压,这将威胁开关设备的可靠性。因此,执行了关于开关条件下开关设备可靠性的研究。基于对瞬态切换过程的分析,获得过电流和过电压。然后,分别建立了用于研究开关设备的绝缘性能和温度升高特性的3D FEM模型,并且计算电场和温度升高。结果表明:1)17.3KV过电压和1.42KA在切换过程中产生过电流; 2)最大场强和温度升高可分别达到3.65 kV / cm和65K,仍然满足开关设备设计标准的要求。