首页> 外文会议>IEEE Electrical Insulation Conference >Comparison of Offline VLF PD Measurements and Online PD Measurements on a 50-Year-Old Hydrogenerator Stator in Norway
【24h】

Comparison of Offline VLF PD Measurements and Online PD Measurements on a 50-Year-Old Hydrogenerator Stator in Norway

机译:在挪威50岁的氢静脉定子上的离线VLF PD测量和在线PD测量的比较

获取原文

摘要

Stator winding insulation is the part of the hydrogenerator experiencing the highest number and the most damaging failures. Partial discharge (PD) measurement, both offline and online, are commonly used for condition assessment and monitoring of electrical machines. The main concern of using very low frequency (VLF) methods is the changed electrical field distributions compared to that at power frequency. Hence, PD measurements performed at VLF should be carefully assessed and compared to PD measurements at power frequencies. In this work, offline PD measurement at VLF are presented and compared to power frequency online measurements of a 50-year-old hydrogenerator in Norway, using statistical analysis of phase resolved PD recordings. It is found that both offline VLF and online assessment can identify unnormal PD activity in a specific phase, although the phase resolved PD patterns are not similar for VLF offline and online assessment.
机译:定子绕组绝缘是体验最高数量和最损坏的故障的氢化机构的一部分。局部放电(PD)测量,离线和在线,通常用于条件评估和电机监控。使用非常低频(VLF)方法的主要关注是改变的电气场分布与功率频率相比。因此,应仔细评估在VLF的PD测量,并与功率频率的PD测量进行比较。在这项工作中,介绍了VLF的离线PD测量,并与挪威50岁的氢化机的功率在线测量相比,使用相位分辨的PD录制的统计分析。发现离线VLF和在线评估都可以在特定阶段识别特定阶段的无通量PD活动,尽管相位解析的PD模式对于VLF离线和在线评估不相似。