Thermal Cycling (TC) test is commonly used for long period of time and in 2012 the standard IEEE 1310 become a recommended practice with details of test parameters and test procedure. Meeting of the specified test parameters is very important. Authors describe their considerations to meet requirements IEEE 1310 for uniformity of the temperature distribution and controlling the copper temperature. IEEE 1310 instruction for cooling air circulation is too restrictive and may not provide the adequate cooling especially for large coils. In the same time standard should provide more guidance for copper temperature measurement. Thermocouple should be installed directly in contact with the conductor for the proper measurements.
机译:热循环(TC)测试通常长时间使用,在2012年,标准IEEE 1310成为了推荐的实践,其中包含测试参数和测试程序的详细信息。满足指定的测试参数非常重要。作者描述了他们的考虑,以满足温度分布均匀性和控制铜温度的IEEE 1310要求。 IEEE 1310关于冷却空气循环的说明过于严格,可能无法提供足够的冷却,特别是对于大型线圈。同时标准应为铜温度测量提供更多指导。热电偶应直接安装在与导体接触的位置,以进行正确的测量。