Concurrent flashover experiments in two parallel arcing horns have been conducted for the clarification of multi-phase faults of transmission lines. In the experiment, we examined influences of line surge impedances on the concurrent flashover. After a flashover in one of arcing horns in transmission lines, the voltage at the other arcing horns decreases. However, the value of the voltage of the arcing horn is greater than 0 because of the line surge impedance. We found that maximum time difference of the flashover between parallel two arcing horns is more than 1 μs. Furthermore, in the case of the maximum time difference, a new type of the flashover processes in the arcing horns was observed. These experiment shows that the influence of the line surge impedance is important.
机译:已经进行了两个并行电弧喇叭的并发闪络实验,以澄清传输线的多相故障。在实验中,我们检查了线浪涌阻抗对并发闪络的影响。在传输线中的电弧喇叭之一中闪过闪光灯之后,另一个电弧喇叭处的电压降低。然而,由于线浪涌阻抗,电弧喇叭电压的值大于0。我们发现,并联两个电弧喇叭之间的闪络的最大时间差超过1μs。此外,在最大时间差的情况下,观察到在电弧喇叭中的新型闪络过程。这些实验表明,线浪阻抗的影响很重要。