首页> 外文会议>IEEE Power and Energy Society General Meeting >Simulation analysis of Arc grounding fault in non-solidly earthed network
【24h】

Simulation analysis of Arc grounding fault in non-solidly earthed network

机译:非固体接地网电弧接地故障的仿真分析

获取原文

摘要

Single-phase arc grounding fault appears in non-solidly earthed network quite frequently. However, most studies are based on the high-current arc models, which are not applicable to non-solidly earthed networks. This paper introduces an improved cybernetic arc model and applies it to the non-solidly earthed network. A simulation model of 10kV distribution network is built via MATLAB. Comparing the simulation results with the experimental results, it indicates that arc characteristics can be reflected effectively by the arc model. Eventually, the influence of different model parameters on arc characteristics is emphatically analyzed.
机译:单相电弧接地故障在非固体接地网络中非常频繁地出现。但是,大多数研究都是基于大电流电弧模型,不适用于非牢固接地的网络。本文介绍了一种改进的控制论弧模型,并将其应用于非固体接地网络。利用MATLAB建立了10kV配电网的仿真模型。将仿真结果与实验结果进行比较,表明电弧模型可以有效地反映电弧特性。最终,着重分析了不同模型参数对电弧特性的影响。