A current transformer saturation identification method of transmission line based on current sample data is proposed in this paper. Mechanism and characteristics of current transformer saturation are analyzed firstly. Current transformer saturation identification plane is proposed. It is divided into three parts: internal fault zone, external fault zone and current transformer saturation zone caused by external faults. For current transformer saturation caused by external faults, current differential protection is blocked. The RTDS simulation results show that the method can identify CT Saturation quickly and sensitively. It is not impacted by data window length.
机译:提出了一种基于电流采样数据的输电线路电流互感器饱和识别方法。首先分析了电流互感器饱和的机理和特性。提出了电流互感器饱和识别平面。它分为三个部分:内部故障区,外部故障区和由外部故障引起的电流互感器饱和区。对于由外部故障引起的电流互感器饱和,电流差动保护被阻止。 RTDS仿真结果表明,该方法可以快速,灵敏地识别CT饱和度。它不受数据窗口长度的影响。