首页> 外文会议>IEEE Power and Energy Society General Meeting >A coordinate strategy of inverter and transformer control modes to improve static voltage stability in AC/DC power systems
【24h】

A coordinate strategy of inverter and transformer control modes to improve static voltage stability in AC/DC power systems

机译:逆变器和变压器控制模式的协调策略,可提高AC / DC电力系统的静态电压稳定性

获取原文

摘要

In this paper, the impacts of inverter control mode switching and converter transformer control modes on the static voltage stability of AC/DC power systems are analyzed based on the quasi-steady-state model of HVDC systems. Based on the mechanism analysis, a new coordinate strategy of control modes of inverter and transformer is proposed to improve the static voltage stability of AC/DC systems. With load increasing, the coordinate strategy aims at keeping the power factor of the inverter as high as possible to minimize the reactive power demands of the DC system. Simulation results demonstrate the correctness of the voltage stability analysis results and the effectiveness of the proposed coordinate strategy.
机译:本文基于HVDC系统的准稳态模型,分析了逆变器控制模式切换和变流器变压器控制模式对交直流电力系统静态电压稳定性的影响。在机理分析的基础上,提出了一种新的逆变器和变压器控制方式协调策略,以提高交直流系统的静态电压稳定性。随着负载的增加,协调策略旨在保持逆变器的功率因数尽可能高,以最小化DC系统的无功功率需求。仿真结果证明了电压稳定性分析结果的正确性和所提出的协调策略的有效性。