首页> 外文会议>IEEE Electrical Power and Energy Conference >Analytic approximation of fault current contributed by DC capacitors in VSC-HVDC pole-to-pole fault
【24h】

Analytic approximation of fault current contributed by DC capacitors in VSC-HVDC pole-to-pole fault

机译:VSC-HVDC极间故障中直流电容器贡献的故障电流的解析近似

获取原文
获取外文期刊封面目录资料

摘要

Based on the travelling wave analysis and Laplace transformation, this paper proposes a new expression for the approximation of current contributed by dc capacitor in VSC-HVDC networks during the pole-to-pole fault. To improve the accuracy of the theoretical analysis, the distributed, frequency-dependent DC line parameters and the skin effect are all considered. Using PSCAD software, a ±200 kV VSC-HVDC transmission system model is constructed, and extensive simulations are performed. Through comparing the analytic approximation calculation with simulation results, the validity and feasibility of the proposed expression are confirmed.
机译:在行波分析和拉普拉斯变换的基础上,本文提出了一个新的表达式,用于在极间故障期间对VSC-HVDC网络中直流电容器贡献的电流进行近似。为了提高理论分析的准确性,所有分布式频率相关的直流线路参数和集肤效应都被考虑了。使用PSCAD软件,构建了±200 kV VSC-HVDC传输系统模型,并进行了广泛的仿真。通过将解析近似计算与仿真结果进行比较,证实了所提表达式的有效性和可行性。