首页> 外文会议>Chinese Automation Congress >Alarm root cause analysis for water level monitoring in high and low pressure heaters of power plants
【24h】

Alarm root cause analysis for water level monitoring in high and low pressure heaters of power plants

机译:电厂高低压加热器水位监测的警报根本原因分析

获取原文

摘要

In order to ensure the safe and economic operations of thermal power plants, heater water levels of high pressure (HP) and low pressure (LP) heaters are important process variables to be monitored in industrial alarm systems. This paper proposes multiple factors affecting heater water levels, and the ways performing the root cause analysis for corresponding alarms. Combining with the operating data of a large-scale 300 MW power generation unit in 2015, the number of each cause is summarized for a large amount of alarms of HP and LP water levels. The results show that excessive movements of control valves are the main causes of alarms for the #7 and #8 low pressure heaters, and changes in power generation load are the main causes of alarms in the #6 low pressure heater. Those analysis results may help operators to obtain the root causes of alarms promptly and take suitable corrective actions to remove alarms for the safe and efficient operation of the high and low pressure heaters.
机译:为了确保火力发电厂的安全和经济运行,高压(HP)和低压(LP)加热器的加热器水位是重要的过程变量,需要在工业报警系统中进行监视。本文提出了影响加热器水位的多种因素,以及对相应警报进行根本原因分析的方法。结合2015年大型300 MW发电机组的运行数据,汇总了造成HP和LP水位大量警报的每种原因的数量。结果表明,控制阀的过度移动是#7和#8低压加热器报警的主要原因,而发电负荷的变化是#6低压加热器报警的主要原因。这些分析结果可以帮助操作员迅速找到警报的根本原因,并采取适当的纠正措施来消除警报,以确保高低压加热器的安全有效运行。