首页> 外文会议>IEEE Region 10 Conference >Inductive coupling method for on-line frequency response analysis (FRA) for transformer winding diagnostic
【24h】

Inductive coupling method for on-line frequency response analysis (FRA) for transformer winding diagnostic

机译:用于变压器绕组诊断的在线频率响应分析(FRA)的电感耦合方法

获取原文

摘要

Based on two-probe inductive coupling and two-port cascade network theorem, in-circuit impedance extraction of primary of operational transformer has been discussed and validated. The importance of this approach is to overcome drawbacks in existing on-line Frequency Response Analysis (FRA) which is used to monitor impedance of the transformer winding to detect movement or deformation of transformer winding and predict early sign of transformer failure. Hence, it can be used for on-line FRA on operational transformer without expensive outage of the system.
机译:基于两探针感应耦合和两端口级联网络定理,讨论并验证了运算变压器原边的在线阻抗提取。这种方法的重要性在于克服现有在线频率响应分析(FRA)中的缺陷,该分析用于监视变压器绕组的阻抗以检测变压器绕组的运动或变形并预测变压器故障的早期迹象。因此,它可用于运行变压器上的在线FRA,而不会造成系统昂贵的停机。