首页> 外文会议>IEEE Power and Energy Society Innovative Smart Grid Technologies Conference >Reliability analysis of 380V DC distribution in data centers
【24h】

Reliability analysis of 380V DC distribution in data centers

机译:数据中心380V直流配电的可靠性分析

获取原文

摘要

Data center downtime causes losses of millions of dollars. Maintaining high availability at all times is very critical to data centers. The distribution system with higher number of components is more likely to fail, resulting in increased downtime. This study presents a 380V DC powering option for data center distribution system, as the number of power conversion stages is less compared to the AC system. This study aims at comparing reliabilities of typical 480V AC distribution architecture against 380V DC architecture. Reliability assessment was done for both AC and DC sytems complying with Tier IV standard, as most of the data center uses Tier IV standard in their distribution system. The analysis was done for different level of redundancy (for eg. N, N+1, N+2) in the UPS system for both AC and DC systems. The reliability data was obtained from IEEE 493 Gold Book. Monte carlo simulation method was used to perform the reliability calculations. The simulation results showed that the 380V DC distribution system has higher level of reliability than conventional 480V ac distribution system in data centers but only up to certain level of redundancy in the UPS system. The reliability level of AC system will approach the reliability level of a DC system when a very high level of redundancy in the UPS system is considered, but this will increase the overall cost of the data center.
机译:数据中心停机会造成数百万美元的损失。始终保持高可用性对数据中心至关重要。具有更多组件的分发系统更有可能发生故障,从而导致停机时间增加。这项研究提出了一种用于数据中心配电系统的380V直流电源选项,因为与AC系统相比,电源转换级的数量更少。本研究旨在比较典型的480V AC配电架构与380V DC架构的可靠性。对符合Tier IV标准的AC和DC系统进行了可靠性评估,因为大多数数据中心在其配电系统中都使用Tier IV标准。针对AC和DC系统的UPS系统中不同级别的冗余度(例如N,N + 1,N + 2)进行了分析。可靠性数据是从IEEE 493 Gold Book获得的。采用蒙特卡罗仿真方法进行可靠性计算。仿真结果表明,在数据中心中,380V直流配电系统具有比常规480V交流配电系统更高的可靠性,但在UPS系统中只能达到一定程度的冗余。当考虑到UPS系统中非常高的冗余级别时,AC系统的可靠性级别将接近DC系统的可靠性级别,但这将增加数据中心的总体成本。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号