首页> 外文会议>IEEE PES Asia-Pacific Power and Energy Engineering Conference >Dependence of over-voltage level of different voltage class surge arrestors on grounding device parameters. Experimental study and simulation
【24h】

Dependence of over-voltage level of different voltage class surge arrestors on grounding device parameters. Experimental study and simulation

机译:不同电压等级电涌放电器的过电压水平取决于接地设备参数。实验研究与仿真

获取原文

摘要

It is demonstrated experimentally at surge protecting device connection to grounding system overvoltage limitation level depends on inductive part of the grounding impedance. Experimental study of resistive-inductive equivalent circuit parameters effect has shown presence of high frequency voltage component with characteristic period 1-3 μs. Depending on the grounding inductance the overvoltage limitation level rises up to 20-40%/. It can substantially reduce the protected equipment life time.
机译:实验证明,在浪涌保护装置与接地系统的连接上,过电压限制水平取决于接地阻抗的感应部分。电阻-电感等效电路参数效应的实验研究表明,存在特征周期为1-3μs的高频电压分量。根据接地电感的不同,过电压限制水平会上升到20-40%/。它可以大大减少受保护设备的使用寿命。