首页> 外文会议>China International conference on electricity distribution >Detection of inrush current in distribution network based on the attenuation factor of current fundamental
【24h】

Detection of inrush current in distribution network based on the attenuation factor of current fundamental

机译:基于电流基波衰减因子的配电网涌流检测

获取原文
获取外文期刊封面目录资料

摘要

Due to the numbers of transformer, the closing angle and other reasons, the inrush current performed intricately, which usually made the protection miss operation. Therefore, reliability and stability in protection of transformer is important task in distribution system. In this paper, an efficient method for detection of inrush current is presented, which is based on the attenuation factor of current fundamental, and the attenuation factor is calculated by the Prony algorithm, which could obtain the amplitude and the phase too. Finally, results in all cases show the reliability and feasibility of this method used a large number of dates which are from PSCAD simulation and actual scene.
机译:由于变压器的数量,闭合角度等原因,浪涌电流表现得很复杂,通常会使保护误动作。因此,变压器保护的可靠性和稳定性是配电系统中的重要任务。本文提出了一种有效的涌流检测方法,该方法基于电流基波的衰减因子,并通过Prony算法计算出衰减因子,也可以得到振幅和相位。最后,在所有情况下的结果表明,该方法使用了大量来自PSCAD模拟和实际场景的数据的可靠性和可行性。