首页> 外文会议>China International conference on electricity distribution >The arcing fault based multi-cycle incipient fault detection for underground cable
【24h】

The arcing fault based multi-cycle incipient fault detection for underground cable

机译:基于电弧故障的地下电缆多周期初期故障检测

获取原文

摘要

This paper proposes a novel method for detecting a multi-cycle incipient fault in an underground cable. The incipient faults are recognized as self-clearing arcing faults and detection method is performed by calculating fault point voltage total harmonic distortion (THD) for all possible distances in the cable. The arc fault is detected when the fault point voltage THD at any assumed fault distance is larger than the threshold. The proposed arcing fault detection method eliminates the effect of fault distance. The proposed incipient fault detection has been verified by PSCAD/EMTDC simulations. Results show that the proposed method is effective and accurate. Lab experiments are also conducted to further validate the proposed detection method.
机译:本文提出了一种检测地下电缆中多周期初期故障的新方法。初期故障被识别为自清除电弧故障,并且通过计算电缆中所有可能距离的故障点电压总谐波失真(THD)来执行检测方法。当在任何假定的故障距离处的故障点电压THD大于阈值时,都会检测到电弧故障。提出的电弧故障检测方法消除了故障距离的影响。 PSCAD / EMTDC仿真已验证了建议的早期故障检测。结果表明,该方法是有效和准确的。还进行了实验室实验,以进一步验证所提出的检测方法。