摘要

When distribution system with non-effectively ground -ed neutral occurs ground fault, the fault current is very small in amplitude, so the faulted location identification accurately is very difficult. To solve this problem, a new algorithm of travelling wave fault location in distribution line based on improved morphological gradient is adopted. The algorithm selects transient current travelling wave of prominent fault signal characteristics, to extract the a-mode of transient current travelling wave by phase-module transformation and to structure morphological filter to filtrate the a-mode. The method of improved morphological gradient extracts the head of this a-mode of travelling wave and achieves accurate fault location through the principle of single terminal location. Theoretical analysis and simulation results show that the principle of the algorithm is simple and its calculation is small.
机译:当具有无效接地的配电系统发生接地故障时,故障电流的幅度很小,因此很难准确地识别故障位置。为了解决这个问题,采用了一种基于改进的形态梯度的配电线路行波故障测距新算法。该算法选择故障信号特征突出的暂态电流行波,通过相模变换提取暂态电流行波的a模式,并构造形态滤波器对a模式进行滤波。改进的形态学梯度方法提取了该行波的a模头,并通过单端定位原理实现了准确的断层定位。理论分析和仿真结果表明,该算法原理简单,计算量小。