首页> 外文会议>Saudi Arabia Smart Grid Conference >Enhancement of power factor correction equipment performance using damping reactors (case study)
【24h】

Enhancement of power factor correction equipment performance using damping reactors (case study)

机译:使用阻尼电抗器提高功率因数校正设备的性能(案例研究)

获取原文

摘要

Overheating in the equipment and conductors can be primarily caused by harmonics in power systems. Decrease of harmonics is considered necessary, especially when capacitor banks exist. Using a detuned harmonic filter is a traditional solution. Current limiting reactors (CLR) can be an economical solution to damp harmonic pollution if installed in the optimal location. In this paper, power system studies, including: load flow, motor starting, and short circuit, are performed when placing CLR in different locations, to find the optimal location. Similarly, limitation of using CLR and costs are discussed. The study suggests CLR to reduce harmonic pollution, while detuned filters are used in case the CLR fails to satisfy the voltage regulation aspects of the network.
机译:设备和导体中的过热可能主要是由电力系统中的谐波引起的。降低谐波被认为是必要的,尤其是在存在电容器组的情况下。使用失谐的谐波滤波器是传统的解决方案。如果将限流电抗器(CLR)安装在最佳位置,则可以作为一种经济的解决方案来抑制谐波污染。在本文中,将CLR放置在不同位置时进行电力系统研究,包括:潮流,电动机启动和短路,以找到最佳位置。同样,讨论了使用CLR的局限性和成本。研究表明,CLR可以减少谐波污染,而在CLR无法满足网络的电压调节要求的情况下,可以使用失谐滤波器。