While preparing a facility for startup, the commissioning process involved 25kV circuit switching that resulted in two voltage transformer (VT) failures. As a result of these failures, the authors conducted a comprehensive investigation of the VT failures. As the investigation proceeded, VT ferroresonance on circuit opening, and high frequency switching transients on closing, emerged as possible root causes of the VT failures. After incorporating extensive transient simulations and three rounds of field transient measurements, the authors designed and implemented a complete solution that included sizing of snubbers to overcome excessive switching transients, and the development of a saturable reactor to protect voltage transformers against the effects of ferroresonance. This paper describes root causes, simulation, field measurements, recommend solutions, and solution implementation. The correlation between field measurements and simulation results show the effectiveness of the implemented solutions.
机译:在准备启动设备的过程中,调试过程涉及25kV电路开关,这导致两次电压互感器(VT)发生故障。由于这些故障,作者对VT故障进行了全面的调查。随着调查的进行,VT开路时出现铁磁谐振,而闭合时出现高频开关瞬变,这可能是VT故障的根本原因。在结合了广泛的瞬态仿真和三轮现场瞬态测量之后,作者设计并实现了一个完整的解决方案,其中包括确定缓冲器大小以克服过多的开关瞬态,以及开发可饱和电抗器以保护电压互感器免受铁磁谐振的影响。本文介绍了根本原因,模拟,现场测量,推荐解决方案和解决方案实施。现场测量结果与仿真结果之间的相关性表明了所实施解决方案的有效性。