首页> 外文会议>IEEE Power and Energy Society General Meeting >Feeder reconfiguration for unbalanced distribution systems with distributed generation: a hierarchical decentralized approach
【24h】

Feeder reconfiguration for unbalanced distribution systems with distributed generation: a hierarchical decentralized approach

机译:具有分布式发电的不平衡配电系统的馈线重新配置:分层分散式方法

获取原文

摘要

Most existing approaches for distribution network reconfiguration assume that the distribution system is (three-phase) balanced and a single-phase equivalent is used. However, distribution feeders are usually unbalanced due to a large number of single-phase loads, nonsymmetrical conductor spacing, and three-phase line topology. This paper builds on our previous work and studies feeder reconfiguration for unbalanced distribution systems with distributed generation (DG). The location and capacity of three-phase DG units are determined using sensitivity analysis and nonlinear programming, and the distribution feeder is reconfigured based on the status of time-varying loads, output power from DG units and faults on the network while minimizing the DG operating costs. Simulation results show the effectiveness and computational efficiency of the proposed approach.
机译:用于配电网重新配置的大多数现有方法都假定配电系统是(三相)平衡的,并且使用了单相等效系统。但是,由于大量的单相负载,不对称的导体间距和三相线路拓扑,配电馈线通常不平衡。本文以我们之前的工作为基础,并研究了具有分布式发电(DG)的不平衡配电系统的馈线重新配置。使用灵敏度分析和非线性编程确定三相DG单元的位置和容量,并根据时变负载的状态,DG单元的输出功率和网络中的故障重新配置配电馈线,同时最大程度地减少DG的运行费用。仿真结果表明了该方法的有效性和计算效率。

著录项