首页> 外文会议>IEEE electrical insulation conference >Partial discharge and aging of AC cable systems under repetitive voltage transient supply
【24h】

Partial discharge and aging of AC cable systems under repetitive voltage transient supply

机译:重复电压瞬态电源下AC电缆系统的局部放电和老化

获取原文

摘要

Transients and repetitive transients affect cable insulation life in a way, which is not easily predictable at the design stage. Therefore, cable system life can be shorter than that expected especially when loads controlled by power electronics are fed, or when HVDC systems are integrated in AC networks. This paper has the purpose to provide a statistical approach to estimate the life of a cable insulation system when repetitive transients, of know probability distribution, are expected to affect insulation during operation. It is shown, using the Miner law and a stochastic approach, that life at a given reliability percentage can be shortened even significantly, depending on transient overvoltage and repetition rate. Condition monitoring, however, remains the main tool to keep track of cable health condition during operation life.
机译:瞬态和重复性瞬态以某种方式影响电缆绝缘寿命,这在设计阶段很难预测。因此,电缆系统的寿命可能比预期的要短,特别是在馈入由电力电子设备控制的负载或将HVDC系统集成到AC网络中时。本文的目的是提供一种统计方法,以估计已知概率分布的重复瞬变会在操作过程中影响绝缘的情况下,估计电缆绝缘系统的寿命。使用Miner定律和随机方法表明,根据瞬态过电压和重复频率,在给定的可靠性百分比下,寿命甚至可以大大缩短。但是,状态监视仍然是在使用寿命期间跟踪电缆健康状况的主要工具。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号