Addition of metal inhibitor to corrosive transformer oil was employed to prevent the formation of semi-conductive Cu2S on copper surface. The formation of impermeable layer is the key process, however, little attention were paid on this process. Here, we performed aging experiment with benzotriazole and benzimidazole type inhibitors on copper strips in corrosive transformer oil. The experiment shows that the N1 position required free coordinating site for the protective layer formation. And molecules with substituent in C2 position are sensitive to the effectiveness of inhibition. Also, DFT calculation was employed to investigate the molecular structure, electronic properties. It is found that none of EHOMO, ELUMO, energy gap and dipole moment is correlated to the structure-reactivity. However, the steric analysis shows strong impact on the impermeable layer formation, suggesting end-on orientation stacking model in the chemisorption process. Furthermore, we afforded inhibiting results by introducing free coordinating size like amino and thiol group at C2 position. These experiments and analysis results offered us deeper understanding to the process of suppression with inhibitor and theoretical guide for inhibitor design in transformer oil.
机译:在腐蚀的变压器油中添加了金属抑制剂,以防止在铜表面形成半导电性的Cu2S。不可渗透层的形成是关键过程,然而,对该过程的关注很少。在这里,我们在腐蚀性变压器油的铜带上使用苯并三唑和苯并咪唑类抑制剂进行了老化试验。实验表明,N1位置需要自由配位位点来形成保护层。而且在C2位置带有取代基的分子对抑制效果很敏感。另外,采用DFT计算来研究分子结构,电子性质。发现EHOMO,ELUMO,能隙和偶极矩均与结构反应性无关。但是,空间分析显示了对不可渗透层形成的强烈影响,表明了化学吸附过程中的端对端方向堆积模型。此外,我们通过在C2位置引入游离配位基团(如氨基和硫醇基)来提供抑制结果。这些实验和分析结果为我们提供了对抑制剂抑制过程的更深入理解,以及变压器油中抑制剂设计的理论指导。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号