This paper describes the design and application of a three-phase device used to isolate a faulted spur from the main feeder. This allows restoration of service to the feeder. Visibly open contacts and provisions for grounding the faulted spur provides the operating conditions for repairing the fault. When the fault is repaired the device can be triggered to close spring-loaded contacts and reconnect the spur to the feeder without interruption of the feeder. The device is designed to operate on a 27kV, 600A system with a fault-close rating of 40kA for 10 cycles.
机译:本文介绍了一种用于隔离主馈线断电器的三相装置的设计和应用。这允许将服务恢复到馈线。明显打开的接触和用于接地的规定为断层刺激提供修复故障的操作条件。当故障被修复时,可以触发装置以关闭弹簧加载的触点并将浇口重新连接到进给器而不中断进料器。该器件设计用于27kV,600A系统,具有40kA的故障级别为10次循环。