Non-intrusive Case Temperature Measurement Method of Direct-water-cooled Power Module

机译:直接水冷功率模块的非侵入式壳体温度测量方法

获取原文

摘要

In this paper, we present a non-intrusive case temperature measurement method of the direct-water-cooled power module. It uses the structure function, which in this case comprises the cumulative thermal capacitance and the cumulative thermal resistance. Since the effective heat transfer rate of the pinfin heatsink varies with the water flow rate, in this study we assumed the inflection point of the structure function corresponding to the change in the flow rate was junction-case thermal resistance. We compared numerical simulation results with experimental results and present our findings. Finally, we show that the design area in which the heat spreading angle of 45 degrees, the well-known rule of thumb, is suitable.
机译:在本文中,我们提出了一种直接水冷式功率模块的非侵入式外壳温度测量方法。它使用结构函数,在这种情况下,该函数包括累积热容和累积热阻。由于针状散热片的有效传热率随水流量的变化而变化,因此在本研究中,我们假设与流量变化相对应的结构函数的拐点是结壳热阻。我们将数值模拟结果与实验结果进行了比较,并提出了我们的发现。最后,我们证明设计区域中的散热角度为45度(众所周知的经验法则)是合适的。