Analysis of earth currents in a medium-voltage distribution network with three-core cables

机译:用三芯电缆分析中压配电网中的接地电流

获取原文

摘要

In this paper a simplified zero-sequence model of a medium-voltage network with three-core cables is proposed. The model is then used to analyze the distribution of earth currents in the network when a phase-to-ground fault occurs in the line between consumer substations. Then this paper studies how this distribution changes when the resistance of earth grids of consumer substations change and when fault location changes. Result shows that a large proportion of earth current flows back to the earth grid of source substation through sheaths and armors of cables instead of flowing to the earth grid of the nearest consumer substation. And this proportion is hardly affected by the resistance of earth grids of consumer substations or by fault location. The theoretical result is testified by simulation using PSCAD.
机译:本文提出了一种具有三芯电缆的中压网络的简化零序模型。然后,当用户变电站之间的线路发生相接地故障时,该模型将用于分析网络中的接地电流分布。然后,本文研究了当用户变电站的接地网电阻变化以及故障位置变化时,这种分布如何变化。结果表明,很大一部分地电流通过电缆的护套和铠装流回到变电站的接地网,而不是流向最近的用户变电站的接地网。而且该比例几乎不受用户变电站的接地网电阻或故障位置的影响。理论结果通过PSCAD的仿真得到验证。