Study of occurrence of overvoltage along power transmission lines with acceptable end voltage

机译:终端电压可接受的输电线路过电压的发生研究

获取原文

摘要

For studies of insulation coordination at industrial frequency transmission line must be modelled with much more details than for other studies, like load flow and short circuit analyses. In other words, that usual representation of the transmission line by a single quadrupole Pi circuit is not applicable. In fact, all of the three-phase conductors must be analyzed separately though the determination of individual voltage profile for several conditions of load. This is so because it is possible that voltage to ground of each conductor presents itself as satisfactory at its ends whereas overvoltage may occur along some points in between them. Thus, an alternative and feasible way for modelling the transmission line is proposed by the authors. Although the proposed method is not new, it is has not been usual. For showing the importance of the proposed method a real 230 kV/197 km transmission line are taken and simulated results do show how the occurrence of overvoltage is possible, not only under fundamental frequency but also for harmonics. All the presented results are a clear evidence of the need in reevaluating some conceptions of insulation coordination for power transmission lines.
机译:对于工业频率传输线的绝缘配合研究,必须以比其他研究(例如潮流和短路分析)更多的细节来建模。换句话说,由单个四极Pi电路对传输线的通常表示是不适用的。实际上,必须通过确定几种负载条件下的单个电压曲线来单独分析所有三相导体。之所以如此,是因为每个导体的接地电压可能在其端部表现出令人满意的水平,而过电压可能会沿着导体之间的某些点发生。因此,作者提出了另一种可行的传输线建模方法。尽管所提出的方法不是新方法,但它并不是通常的方法。为了表明所提出方法的重要性,采用了一条真实的230 kV / 197 km输电线路,仿真结果确实显示了不仅在基频下而且在谐波情况下如何可能发生过电压。所有给出的结果清楚地证明了需要重新评估输电线路绝缘配合的某些概念。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号