首页> 外文会议>IEEE International Power Modulator and High Voltage Conference >Study on sweep frequency impedance method for detecting internal winding short circuit fault in power transformer
【24h】

Study on sweep frequency impedance method for detecting internal winding short circuit fault in power transformer

机译:电力变压器内部绕组短路故障检测扫描频率阻抗方法研究

获取原文

摘要

Power transformers are commonly considered to be the heart of the transmission and distribution sectors of power systems. Base on statistics of failure in power transformers over several years, undetected short circuit fault is the primary cause of power transformer failure. At present, frequency response analysis (FRA) is one of the well-recognized diagnostic tools for detecting winding faults, but it has some defects, such as an imperfect standard code and instability caused by the onsite electromagnetic noise. This paper proposes a novel method named sweep frequency impedance (SFI) to address the difficulties arising from FRA. Based on this new method, a highly accurate, fast, economical, and nondestructive testing system was established to diagnose the short circuit fault imposed on windings of an oil-immersed testing transformer. The experimental results show that the newly designed monitoring system is feasible and sensitive to detect a short circuit fault and has a clear evaluation criterion. It gives the current state of a transformer by constructing a SFI locus diagram, which is more stable and smoother than a FRA curve, in the frequency range between 10 Hz and 1 MHz. The values of 50 Hz in the SFI curves are basically equal to the short circuit impedance (SCI) value on the nameplate of the transformer, so they can be used to compare with that of the healthy transformer for recognizing a short circuit fault. Moreover, the changes of the SFI curve, which is similar as the FRA curve, can be used to judge the short circuit fault.
机译:电力变压器通常被认为是电力系统的传输和分配扇区的核心。基于多年来电力变压器故障的统计数据,未检测到的短路故障是电源变压器故障的主要原因。目前,频率响应分析(FRA)是检测绕组故障的公认诊断工具之一,但它具有一些缺陷,例如不完美的标准码和由现场电磁噪声引起的不稳定性。本文提出了一种名为扫描频率阻抗(SFI)的新型方法,以解决FRA所产生的困难。基于这种新方法,建立了高度准确,快速,经济,无损检测系统,以诊断油浸式测试变压器绕组施加的短路故障。实验结果表明,新设计的监控系统是可行和敏感的,以检测短路故障并具有明确的评估标准。它通过构建SFI基因座图来提供变压器的当前状态,该SFI轨迹图比FRA曲线更稳定,更光滑,在10Hz和1MHz之间的频率范围内。 SFI曲线中50Hz的值基本上等于变压器的铭牌上的短路阻抗(SCI)值,因此它们可用于与健康变压器的铭牌进行比较,以识别短路故障。此外,SFI曲线的变化与FRA曲线类似,可用于判断短路故障。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号