首页> 外文会议>International Conference on Electrical Engineering and Computer Science >Evaluation of grounding system for AC substation using sub-ground (SG) software for novice professionals: Interpretation based on IEEE Std. 80-1986
【24h】

Evaluation of grounding system for AC substation using sub-ground (SG) software for novice professionals: Interpretation based on IEEE Std. 80-1986

机译:新手专业人才使用子地(SG)软件对AC变电站接地系统的评价:基于IEEE STD的解释。 80-1986

获取原文

摘要

Grounding system plays very important role in AC substation station for person and equipment safety. Proper design of grounding system is achievable by following IEEE Std-80 on safety in AC substation grounding but novice professionals find it not easy to use. The advantage of this paper presents evaluation of grounding system for AC substation by case studies presentation thus easing the understanding of IEEE Std-80 and its usage. This was carried out by using homegrown Sub-ground software with capability to identify the safety status of a grounding system design procedures. The grounding system is evaluated with six different cases. Different parameter is changed in each case to observe the result of the grounding system. The result shows that there are several important parameters in designing a grounding system. The parameters are grounding grid size, number of parallel rod, level of fault current, crush rock layer, cross sectional area of ground rod and level of soil resistivity. The tolerable and calculated step and touch voltage as well as the mesh voltage of the grounding system are presented in manner to tutor novice professionals on AC grounding system design. Last but not least the software developed in the laboratory useful for novice professionals training for AC substation grounding system.
机译:接地系统在交流变电站的人和设备安全中起着非常重要的作用。通过在AC变电站的安全性接地的IEEE STD-80遵循IEEE STD-80,可以实现适当的接地系统设计,但新手专业人员发现它不易使用。本文的优点是通过案例研究表现出对AC变电站接地系统的评估,从而缓解了对IEEE STD-80及其使用的理解。这是通过使用本土的子地区软件进行的,能够识别接地系统设计程序的安全状态。接地系统被评估为六种不同的情况。在每种情况下更改不同的参数以观察接地系统的结果。结果表明,在设计接地系统时存在几个重要参数。该参数是接地网格尺寸,平行杆数,故障电流水平,粉碎岩层,地面横截面积和土壤电阻率水平。可容忍和计算的步骤和触摸电压以及接地系统的网格电压以AC接地系统设计的导师新手专业人员提供。最后但并非最不重要的是,在实验室中开发的软件可用于交流变电站接地系统的新手专业人士培训。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号