摘要

Composite insulators are widely used in transmission lines. Performance degradation of material is more and more urgent with operation time increases. In China Southern Power Grid, some composite insulators in-service suffer partial abnormal temperature rise which has been a serious potential hazard to operation of transmission lines. In this paper, a 500 kV AC composite insulator with partial abnormal temperature rise, was analyzed. By dissecting these insulators, FRP rod corrosion with varying degrees were found along the string. After that, chemical compositions on FRP rod corrosion surface were examined by XPS (X-Ray Photoelectron Spectroscopy). Test results showed that the basic elements, carbon, nitrogen and oxygen changes according to certain rules and the chain number of Si-O increases when corrosion degree aggravate. Analysis on change of chemical element reveals that the FRP rod corrosion of the composite insulators with partial abnormal temperature rise is mainly due to oxidation.
机译:复合绝缘子广泛用于传输线。随着操作时间的增加,材料的性能下降越来越迫切。在南方电网,一些在役的复合绝缘子的温度局部升高,这对输电线路的运行造成了严重的潜在危害。本文分析了部分异常温升的500 kV交流复合绝缘子。通过解剖这些绝缘子,发现在玻璃钢串上有不同程度的FRP棒腐蚀。之后,通过XPS(X射线光电子能谱)检查FRP棒腐蚀表面上的化学成分。试验结果表明,随着腐蚀程度的加剧,碳,氮,氧等基本元素发生一定变化,Si-O的链数增加。化学元素变化的分析表明,复合绝缘子的FRP棒腐蚀(局部温度异常升高)主要是由于氧化引起的。