首页> 外文会议>ASME heat transfer conference >ENERGY CONSERVATION MEASURES OF A PRIMARY DATA CENTER ON AN ACADEMIC CAMPUS
【24h】

ENERGY CONSERVATION MEASURES OF A PRIMARY DATA CENTER ON AN ACADEMIC CAMPUS

机译:高校校园数据中心的节能措施

获取原文

摘要

Energy Conservation Measures (ECMs) of the primary data center at the University of Maryland are developed. Measurement and simulation are performed to validate the developed ECMs. Three ECMs - 1) Increase in the return temperature at Computer Room Air Conditionings (CRACs) 2) Cold aisle containment 3) Elimination of unnecessary CRACs -are suggested to reduce energy consumption by optimizing the thermo-fluid flow in the data center. Power savings of 12.7 kW - 17.4 kW and 14.1 kW are obtained by increasing the return air temperatures at the CRACs and performing the cold aisle containment, respectively. In addition, a power saving of 11.2 kW is obtained by turning off CRACs 3 and 8 which have an adverse effect on the data center cooling.
机译:制定了马里兰大学主要数据中心的节能措施(ECM)。进行测量和仿真以验证已开发的ECM。三个ECM-1)升高机房空调(CRAC)的返回温度2)封闭冷通道3)消除不必要的CRAC-建议通过优化数据中心的热流体流量来减少能耗。通过提高CRAC处的回风温度并执行冷通道封闭,分别可节省12.7 kW-17.4 kW和14.1 kW。另外,通过关闭对数据中心冷却有不利影响的CRAC 3和8,可以节省11.2 kW的功率。