首页> 外文会议>International Conference on Information Science, Electronics and Electrical Engineering >The optimization of 750kV anti-ice-flashing composite insulator string
【24h】

The optimization of 750kV anti-ice-flashing composite insulator string

机译:750kV防冰闪复合绝缘子串的优化

获取原文

摘要

Composite insulators have been widely used for its excellent flashover endurance capability, but the umbrella of standard composite insulators are easily been bridged in icing condition. Flashover problems caused by icing insulator have a serious threat to the safe operation of transmission lines,. It is the key technologies for the safe operation of power system which should be solved as soon as possible. The influence of two types of composite insulator umbrella structure (common type and anti-ice type) on iced AC flashover voltage characteristics in the same structure length, as well as same artificial pollution and artificial icing test conditions, but also the method of artificial iced flashover test on composite insulator were introduced. Iced flashover test results showed that the ice bridge formation could be prevented or extended if the umbrella structure design of anti-ice-type composite insulators was more reasonable. For the 750kV composite insulator under the same conditions of artificial pollution test (SDD/NSDD=0.08/0.48mg/cm) and artificial icing test (when icing water converted to 20 °C, the conductivity is 100μS/cm and the iced thickness from 15mm), it is shown that AC iced flashover voltage of Anti-ice type increased 12%∼28% than common type. Upon the existent theoretical and experimental results and based on a great of laboratory investigations carried out in environment laboratory of China UHV AC test base, for the first time this paper studies systematically the insulators shed optimization which will contribute to the designation for Ultra-UHV anti-icing composite insulators.
机译:复合绝缘子因其出色的耐飞弧性而被广泛使用,但是标准复合绝缘子的伞状结构在结冰条件下很容易桥接。由结冰绝缘子引起的闪络问题严重影响了输电线路的安全运行。电力系统安全运行的关键技术应尽快解决。两种复合绝缘子雨伞结构(普通型和防冰型)对相同结构长度,相同人工污染和人工结冰试验条件下的冰交流闪络电压特性的影响,以及人工冰的方法介绍了复合绝缘子的闪络试验。冰闪试验结果表明,如果防冰型复合绝缘子的伞形结构设计更加合理,则可以防止或延长冰桥的形成。对于750kV复合绝缘子,在相同的人工污染试验(SDD / NSDD = 0.08 / 0.48mg / cm)和人工结冰试验(结冰水转化为20°C时)下,电导率为100μS/ cm,结冰厚度为15mm),表明Anti-ice类型的AC冰击穿电压比普通类型增加了12%〜28%。基于现有的理论和实验结果,并在中国特高压交流试验基地的环境实验室进行的大量实验室研究的基础上,本文首次系统地研究了绝缘子脱落的优化方法,这将有助于设计超特高压抗电绝缘子。覆冰复合绝缘子。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号