Reliability evaluation to converter transformers of 2×12-pulse UHVDC transmission system

机译:2×12脉冲特高压直流输电系统换流变压器的可靠性评估

获取原文

摘要

The converter transformers (CTs) between the AC system and the converters are necessary for reliable operation of the ultra high voltage DC (UHVDC) system. Compared with the traditional HVDC system, 2×12 pulse UHVDC system has more complicated configuration and more capacity levels; the CTs with Y/Y and Y/Δ connections can't be replaced by each other, adding difficulty to the reliability evaluation, which has not be fully investigated yet. In this paper, reliability of the CTs for UHVDC system is quantified using the State Space (SS) and Frequency & Duration (F&D) methods. The state spaces of the single-phase CTs with three- and two-windings are proposed. Six operating modes are defined for the CTs. The spare for the three- and two- winding CTs is considered. The two-winding CTs with Y/Y and Y/Δ connections are differentiated and modelled separately to reduce number of the states. The numerical results are compared with the existing literatures to show accuracy and advantage of the proposed model.
机译:交流系统和转换器之间的转换器变压器(CT)是超高压直流(UHVDC)系统可靠运行所必需的。与传统的高压直流输电系统相比,2×12脉冲超高压直流输电系统配置更为复杂,容量等级更高; Y / Y和Y /Δ连接的CT不能相互替换,增加了可靠性评估的难度,目前尚未进行充分研究。在本文中,使用状态空间(SS)和频率与持续时间(F&D)方法对特高压直流输电系统CT的可靠性进行了量化。提出了具有三绕组和二绕组的单相CT的状态空间。为CT定义了六种操作模式。考虑了三绕组和二绕组CT的备件。对具有Y / Y和Y /Δ连接的双绕组CT进行区分和建模,以减少状态数。将数值结果与现有文献进行比较,以显示所提出模型的准确性和优势。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号