首页> 外文会议>China International conference on electricity distribution >The research of insulator model based on ATP-EMTP
【24h】

The research of insulator model based on ATP-EMTP

机译:基于ATP-EMTP的绝缘子模型研究

获取原文

摘要

Performance of power transmission lines has a great impact on reliability of a particular power supply system of a country. Unreliable power transmission lines can even lead to total power failures resulting with great financial losses. The lightning back flashover effects are recognized as one of the major causes of transmission line outages. In the research on lightning resisting level of transmission lines, the definition acquired by standard wave experiment is applied to judge the flashover of lighting over-voltage at both ends of insulators, but the result of lighting protection calculation on the basis of this method is conservative. This paper introduces a model based on continuous leader development. Taking 500kv transmission lines for example and using simulation program software ATP-EMTP to calculate the lighting resisting levels. The lighting resisting levels under different flashover criteria are compared. Results of the research show that comparing with traditional criterion, the model based on the development of continuous leaders is more accurate.
机译:输电线路的性能对一个国家的特定电源系统的可靠性有很大的影响。不可靠的输电线路甚至可能导致全部断电,从而造成巨大的财务损失。雷电闪络效应被认为是传输线中断的主要原因之一。在输电线路抗雷等级的研究中,采用标准波实验获得的定义来判断绝缘子两端的雷电过电压的闪络,但基于该方法的雷电保护计算结果较为保守。 。本文介绍了基于持续领导者发展的模型。以500kv输电线路为例,并使用仿真程序软件ATP-EMTP计算耐光等级。比较了不同闪络标准下的耐光等级。研究结果表明,与传统准则相比,基于连续领导者发展的模型更为准确。

著录项