Harmonic components based protection strategy for inverter-interfaced AC microgrid

机译:基于谐波接口AC微电网的基于谐波组件的保护策略

获取原文

摘要

In the inverter-interfaced AC microgrid (IIAM), when a short-circuit fault occurs at the distribution line, the output fault current of inverter is commonly limited to two times over its rated current due to the limited overcurrent capacity of power electronic device. Therefore, the conventional overcurrent protection principle cannot be applied to IIAM. Aiming at addressing this issue, a new protection method based on the low harmonics components is proposed in this paper. Through injecting a certain proportion of fifth harmonics to the fault current, the protection device can detect the fault according to the low harmonics components extracted by the digital relay (DR). This scheme does not rely on the large fault current. Therefore, some limitations of the traditional overcurrent protection are avoided. The corresponding experiments were carried out with two 10kVA parallel-connected inverters supply system, and the results proved the feasibility of this approach.
机译:在逆变器接口的AC微电网(IAM)中,当在配电线路发生短路故障时,由于电力电子设备的过电容有限,逆变器的输出故障电流通常限于其额定电流的两倍。因此,传统的过电流保护原理不能应用于IIAM。旨在解决这个问题,本文提出了一种基于低谐波组件的新保护方法。通过向故障电流注入一定的第五次谐波,保护装置可以根据数字继电器(DR)提取的低谐波组件来检测故障。该方案不依赖于大故障电流。因此,避免了传统过流保护的一些局限性。通过两个10kVA平行连接的逆变器供应系统进行相应的实验,结果证明了这种方法的可行性。