首页> 外文会议>International Conference on Electrical Insulating Materials >Paper moisture variation vs. mechanical deformation impacts on transformer frequency response spectrum
【24h】

Paper moisture variation vs. mechanical deformation impacts on transformer frequency response spectrum

机译:纸张水分变化与机械变形的关系对变压器频率响应谱的影响

获取原文

摘要

Frequency Response Analysis (FRA) has been in use as a diagnostic method for transformers since the last decade and is emerging as a popular technique. However, accurate interpretation of FRA measurements is still under development. Recent studies reveal that apart from winding deformation, FRA data can also be influenced by moisture variation in transformer paper insulation. A better understating of this issue can in turn improve the frequency response interpretation Hence, a specific model transformer was fabricated for this study and the experiment was concentrated on the paper moisture variation and mechanical deformation influences on FRA spectrum deviation. Different physical changes to the test object are investigated and the results are recorded and discussed. These enable comparison of insulation characteristic and mechanical defect impacts on FRA data, and reveal factors influencing the FRA spectrum.
机译:自最近十年以来,频率响应分析(FRA)一直被用作变压器的诊断方法,并且正在成为一种流行的技术。但是,FRA测量值的准确解释仍在开发中。最近的研究表明,除了绕组变形外,FRA数据还可能受变压器纸绝缘中水分变化的影响。对这个问题的更好的低估可以反过来改善频率响应的解释,因此,为该研究制造了一个特定的模型变压器,并且实验集中在纸张水分变化和机械变形对FRA频谱偏差的影响上。研究了测试对象的不同物理变化,并记录和讨论了结果。这些可以比较绝缘特性和机械缺陷对FRA数据的影响,并揭示影响FRA光谱的因素。