IMPROVING CAMPUS CHILLED WATER SYSTEMS WITH INTELLIGENT CONTROL VALVES: A FIELD STUDY

机译:用智能控制阀改善校园冷却水系统:田间研究

获取原文

摘要

The degradation of the temperature difference between supply and return flow, known as AT degradation, in chilled water systems has been widely observed and documented over the last 25 years. High pumping energy consumption as well as reduced efficiency of the chillers operating under part-load conditions, lead to a decrease of overall system efficiency of chilled water plants. This article describes a field study conducted on two university campuses in Massachusetts and Colorado during the cooling season of 2011. The purpose of this experimental study was to alleviate △T degradation problems on both campuses through the use of intelligent pressure-independent control valves, and to quantify the improvements achieved. The MA field results revealed that the intelligent control valves when coupled with a △T management strategy have allowed the campus to serve additional cooling load on its campus with the same distribution and central plant system.
机译:在过去25年中,广泛观察并记录了在冷冻水系统中的供应和返回流量之间的温差降低。高泵送能耗以及减少在部分负荷条件下运行的冷却器的效率,导致冷冻水厂的整体系统效率降低。本文介绍了在2011年冷却季节在马萨诸塞州和科罗拉多州的两大校园开展的田间研究。该实验研究的目的是通过使用智能压力无关的控制阀来缓解两种校区的劣化问题量化实现的改进。 MA场的结果显示,与△T管理策略相结合的智能控制阀允许校园在其校园内使用相同的分布和中央植物系统服务额外的冷却负荷。