首页> 外文会议>Corrosion conference and expo >Correcting Non-uniform Potential distribution and Interference Problems in the Cathodic Protection System of a Gas Compressor Station
【24h】

Correcting Non-uniform Potential distribution and Interference Problems in the Cathodic Protection System of a Gas Compressor Station

机译:纠正气体压缩机站阴极保护系统中不均匀的电位分布和干扰问题

获取原文

摘要

After a period of 12 years of operation of the cathodic protection system in a gas compressor stations, the CP potential distribution hadthanged for various reasons, such as pipelines coating degradation, isolating flanges failures, alterations in pipeline systems, and reinforced concrete foundation (RCF) systems. Isolating flanges failures creates galvanic corrosion between the pipelines and the Cu grids of the earthing system, and the steel rods in the RCF, which consumes part of the CP currents, thus non-uniform potential distribution. The extent of CP current required had become so high that was beyond the capacity of the rectifiers. Some areas had become seriously underprotected and some others seriously overprotected. Meanwhile the interference with other neighboring foreign buried pipeline, also had increased. In this paper the results of correcting measures for these problems is reported.
机译:在气体压缩机站中的阴极保护系统运行了12年之后,CP电位分布由于各种原因而有所降低,例如管道涂层退化,隔离法兰失效,管道系统发生变化以及钢筋混凝土基础(RCF)系统。隔离法兰故障会在接地系统的管道和Cu网格以及RCF中的钢棒之间消耗电腐蚀,从而消耗部分CP电流,从而造成电位分布不均匀。所需CP电流的范围已经变得如此之大,以至于超出了整流器的能力。一些地区受到严重的保护不足,而另一些地区则受到过度保护。同时,对其他相邻的国外埋地管道的干扰也有所增加。本文报告了针对这些问题的纠正措施的结果。