首页> 外文会议>IEEE electrical insulation conference >Comparison of polymeric insulation materials on failure development in low-voltage underground power cables
【24h】

Comparison of polymeric insulation materials on failure development in low-voltage underground power cables

机译:聚合物绝缘材料对低压地下电力电缆故障开发的比较

获取原文

摘要

Sustainable developments impose increasing pressure on Low Voltage (LV) underground power cables, leading to an increasing interest in condition assessment for LV systems. LV cables have been designed mainly on mechanical considerations taking insulation of low voltage levels for granted. However, concerns on degradation aspects is now growing. To make a comparison of insulation materials, water cycling tests on artificially damaged cable sections have been performed. The results show that the material has a major role in degradation rate due to local decomposition upon dry-band arcing, as can also be expected from chemical point of view. Chemical compounds add pollution to the damaged spot, enhancing degradation. PVC shows fastest degradation rate compared to polyurethane and XLPE respectively. These results can be considered in optimal cable design. In addition, aspects like water tightness should also be considered.
机译:可持续发展对低压(LV)地下电力电缆施加了越来越大的压力,导致LV系统条件评估的兴趣日益增长。 LV电缆主要设计于机械考虑,以防止低电压电平进行理所当然。然而,对退化方面的担忧现在正在增长。为了进行绝缘材料的比较,已经进行了人工损坏的电缆部分的水循环试验。结果表明,由于在干频弧线上局部分解,该材料在降解速率方面具有重要作用,也可以从化学观点中预期。化学化合物为损坏的位置增添污染,提高降解。与聚氨酯和XLPE相比,PVC分别显示出最快的降解速率。这些结果可以在最佳电缆设计中考虑。此外,还应考虑水密封性等方面。